Technical guides, planning tools and documents for medical gas projects. The guides summarise the standards; always design to the full standard your project specifies.
Technical guides
Short answers to the questions we hear on projects.
How a medical gas pipeline is organised
Supply, pipeline control and the bedside
How a medical gas pipeline is organised
Supply, pipeline control and the bedsideA medical gas pipeline system has three parts: the supply, the distribution pipeline and the terminal units where staff connect equipment to the patient.
- Oxygen usually has a primary supply, a secondary supply and an emergency reserve; where the primary supply is a VIE (liquid oxygen tank), the secondary supply can be another VIE, a liquid tank or an automatic cylinder manifold.
- Plant alarm conditions are sent to the central alarm system.
- Line valve assemblies and area valve service units (AVSUs) isolate parts of the pipeline.
- Area alarms monitor the pipeline between the AVSU and the terminal units, so there must be no other isolation in that section apart from MSU valves.
Source: HTM 02-01 Part A: 5.59, 6.85, 6.107, 14.41–14.42
Area valve service units (AVSUs)
Where they go and what they need
Area valve service units (AVSUs)
Where they go and what they need- Mount AVSUs between 1 m and 1.8 m so staff can operate them without stooping or over-reaching.
- Arrange the valves in the same order as the terminal units, for example O₂, N₂O, MA, SA, VAC, CO₂.
- Fit specific signage and a schematic at each AVSU showing the area and terminal units it isolates.
- Install departmental AVSUs outside the departments they serve, on the hospital street side of the entrance doors.
- Provide a local alarm for each AVSU.
Source: HTM 02-01 Part A: 3.58, 3.62, 3.63, 3.66
Critical emergency supply
Extra resilience for critical areas
Critical emergency supply
Extra resilience for critical areasWhere specific areas need resilience beyond the three standard sources of supply, a critical emergency supply can be provided. Compressed gas cylinders are usually the appropriate source.
- The emergency manifold joins the pipeline upstream of the AVSU that feeds the area.
- It connects through a non-return valve on the main pipeline.
Source: HTM 02-01 Part A: 6.93–6.94
Medical copper pipe
What to specify
Medical copper pipe
What to specify- Medical gas pipelines use copper pipe to EN 13348: seamless, deoxidised high-purity copper (Cu-DHP) with a clean inner surface.
- Medicabay supplies pipe sizes of 8, 10, 12, 15, 22, 28, 35, 42, 54, 76 and 108 mm, in coils or 5 m lengths.
- Use the pipe size check to estimate the pressure drop and the smallest pipe for your gas, flow and run length.
Source: EN 13348; Medicabay medical copper pipes
Plan the pipeline
Free tools for a first estimate; our engineers check the final design.
Catalogue and standards
Ask our engineers.
Send your drawings and the standard you work to; we review the medical gas design with you.